IMPULSE•G+/VG+ Series 4 Technical Manual
November 2022
Page 138
5.5.5 Profibus-DP (SI-P3) Option Card Setup
Settings for the Profibus-DP communication option card SI-P3.
Table 5-69: SI-P3 Parameter Settings
Parameter
Display
Function
Range
Default
F06-01
Comm Bus Flt Sel
Stopping method at communication error
0–4
1
0 Decel to Stop
1 Coast to Stop
2 Fast-Stop
3 Use B3-03 Method
4 Alarm Only
F06-02
EF0 Detection
Option External Fault
0, 1
0
0 Always Detected
1 Only During Run
F06-03
EF0 Fault Action
Option External Fault
0–4
1
0 Decel to Stop
1 Coast to Stop
2 Fast-Stop
3 Use B3-03 Method
4 Alarm Only
F06-04
BUS Err Det Time
Maximum time the VFD should wait for a
communication error to occur (bUS).
0.0–5.0 sec
2.0
F06-06
Torq Ref/Lmt Sel
Torque Reference Limit Selection (FLV only)
0, 1
0
0 Disabled
1 Enabled
F06-07
Fref PrioritySel
Selects how multi-step speed inputs are
treated when the NetRef command is set.
0, 1
0
0 Net/Com REF
Multi-step reference disabled
1 MultiStep Speed
Multi-step reference enabled
F06-08
Com Prm Init Sel
Determines whether communication-related
parameters (F06-xx and F07-xx) are reset
when the VFD is initialized using A01-05.
0, 1
0
0 Init Com Prms
Communication-related parameters (F06-xx
and F07-xx) are not reset when the VFD is
initialized using A01-05.
1 No Init Com Prms
Reset all communication-related parameters
(F06-xx and F07-xx) when the VFD is
initialized using A01-05.
F06-30
PB Node Address
Node address
0–125
0
F06-31
PB Clear Select
Determines the operation when a “Clear
Mode” command is received.
0, 1
0
0 Reset to Zero
Resets VFD operation with a Clear mode
command.
1 Hold Prev Value
Maintains the previous operation state when
Clear mode command is given.