5.2.18 Digital Input (DI-A3, S4I, or S4IO) Option Card Setup
Selects the digital input controls for the DI-A3, S4I, or S4IO option cards. Additionally, these inputs can be used
virtually via serial communications (C09-01 = 5) over Modbus RTU on the R+,R-,S+,S- interface board terminals or
from the communication option cards.
Table 5-34: Digital Input Setup Parameter Settings
*
for MFDI selections. The following functions will not operate: 20~20F, 31, 34, 35, 47, 80, or 81.
Parameter
Display
Function
Range
Default
C09-01
Digital In Sel
Provides additional programmable MFDI
0–2, 5
0
0 Disabled
No additional MFDI are being used.
1 Enabled S4IO
S4IO or S4I card is installed
2 Enabled DI-A3
DI-A3 card is installed
5 Serial
Serial communication using C09-02–C09-17
Parameter
Display
Terminal Designation
Range
Default
DI-A3
S4I
S4IO
C09-02*
DIO Terminal 1
0
I1
I1
00–FF
0F
C09-03*
DIO Terminal 2
1
I2
I2
00–FF
0F
C09-04*
DIO Terminal 3
2
I3
I3
00–FF
0F
C09-05*
DIO Terminal 4
3
I4
I4
00–FF
0F
C09-06*
DIO Terminal 5
4
-
-
00–FF
0F
C09-07*
DIO Terminal 6
5
-
-
00–FF
0F
C09-08*
DIO Terminal 7
6
-
-
00–FF
0F
C09-09*
DIO Terminal 8
7
-
-
00–FF
0F
C09-10*
DIO Terminal 9
8
-
-
00–FF
0F
C09-11*
DIO Terminal 10
9
-
-
00–FF
0F
C09-12*
DIO Terminal 11
A
-
-
00–FF
0F
C09-13*
DIO Terminal 12
B
-
-
00–FF
0F
C09-14*
DIO Terminal 13
C
-
-
00–FF
0F
C09-15*
DIO Terminal 14
D
-
-
00–FF
0F
C09-16*
DIO Terminal 15
E
-
-
00–FF
0F
C09-17*
DIO Terminal 16
F
-
-
00–FF