IMPULSE•G+/VG+ Series 4 Technical Manual
November 2022
Page 142
Table 5-72: Multi-Function Digital Inputs (MFDI) selectable for H01-0x and C09-0x
Display
Function
0 Multi-Step Ref 2
Multi-Step Reference 2
1 Multi-Step Ref 3
Multi-Step Reference 3
2 Multi-Step Ref 4
Multi-Step Reference 4
3 Multi-Step Ref 5
Multi-Step Reference 5
4 Speed Hold 2
Speed Hold 2 (2nd Step of Three-Step Infinitely Variable)
5 Accel Command
Accel Command (2nd Step of Two-Step Inf. Var. or 3rd Step of Three-Step Inf. Var.)
6 Upper Lmt 1 N.O.
Upper Limit - Slow Down; Normally Open. UL1 - blinking
7 Upper Lmt 2 N.O.
Upper Limit - Stop; Normally Open. UL2 - blinking
8 Lower Lmt 1 N.O.
Lower Limit - Slow Down; Normally Open. LL1 - blinking
9 Lower Lmt 2 N.O.
Lower Limit - Stop; Normally Open. LL2 - blinking
A Upper Lmt 1 N.C.
Upper Limit - Slow Down; Normally Closed. UL1 - blinking
B Upper Lmt 2 N.C.
Upper Limit - Stop; Normally Closed. UL2 - blinking
C Lower Lmt 1 N.C.
Lower Limit - Slow Down; Normally Closed. LL1 - blinking
D Lower Lmt 2 N.C.
Lower Limit - Stop; Normally Closed. LL2 - blinking
E M-Speed Gain 1
Micro-Speed multiplier 1. Gain is set by parameter C02-01. (Priority over Micro-Speed 2)
F Not Used
No function - Terminal is disabled.
10 M-Speed Gain 2
Micro-Speed multiplier 2. Gain is set by parameter C02-02.
11 Load Float 1
Load Float Hold - During run, Load Float will remain On and Fref is held at 0 Hz.
12 Weight Lmt N.C.
Weighted Upper Limit - UL3. Uses C03-08 stopping method and requires manual reset.
13 Swift/Ultra-Lift Enable
Ultra/Swift Lift Enable (C06-01 = 2 or 4). Not Available for Traverse Motion.
14 Alt T-Lim Gain
Alternate Torque Limit Gain - C07-05 to C07-07. Use when Load Testing a Hoist.
15 Forward Jog
Forward Jog (Uses B01-17 Reference)
16 Reverse Jog
Reverse Jog (Uses B01-17 Reference)
17 Forward Inch
Forward Inch
18 Reverse Inch
Reverse Inch
19 Inch Repeat
Inch Repeat
1A Acc/Dec 2
Acceleration/Deceleration Time Changeover 2 using B05-03 and B05-04
1B Acc/Dec 3
Acceleration/Deceleration Time Changeover 3 using B05-12 and B05-13
1C Acc/Dec 4
Acceleration/Deceleration Time Changeover 4 using B05-14 and B05-15
1D Digital Chngover
Analog/Digital Reference Changeover; When B01-18 = 1 On: Digital
1F Run/Ref Src 1/2
Run/Ref Source 2 Switch - On: B03-15/B03-16; Off: B03-01/B03-02 (ignores S1/S2 inputs)
20 through 2F
External Fault Selection (
)
30 Program Lockout
When input is OFF, parameter changes disabled except freq. reference (U01-01).
31 Local/Remote Sel
Local/Remote Changeover. On: Local
32 Ext BaseBlk N.O.
External Baseblock - Normally open (On: Backblock)
33 Ext BaseBlk N.C.
External Baseblock - Normally closed (Off: Backblock)
34 Spd/Trq Chngover
Speed/Torque Control Changeover (On: Torque Control)
35 Load Float 2
Zero Speed initiated. Manual Load Float Timed by C04-01.
36 Polarity Rev
Polarity Reversing command for External Torque Control. On: Reverse Polarity
37 ASR Gain Switch
On: Switches to ASR Gain 2 parameters - Forces D04-07.
38 Acc/Dec RampHold
Speed Hold 1 - Accel/decel is stopped by ON, and frequency is held.
39 OH2 Alarm Signal
External OH2 - VFD overheat protection (OH2 is shown by ON.) (Alarm Only)