IMPULSE•G+/VG+ Series 4 Technical Manual
November 2022
Page 149
* This output does not have an inverse output
** Contact will open when power is disconnected
2D Lower Limit 1
ON: LL1 is detected
OFF: Normal operation
2E Lower Limit 2
ON: LL2 is detected
OFF: Normal operation
30 Lower Limit
ON: LL1 or LL2 is detected
OFF: Normal operation
31 Up/Low Limit
ON: UL1, UL2, UL3, LL1, or LL2 is detected
OFF: Normal operation
32 Snap Shaft
ON: VFD has detected a Snap Shaft
OFF: Normal operation
34 Index Complete
ON: Index move is complete
OFF: Normal operation or Index move is not complete
35 Ready for F-Ref
ON: C08-04 timer has expired or Brake Answerback is detected H01-xx = 58
OFF: Normal operation or VFD detected a BE1, BE2, BE4 alarm or is stopped.
36 Fan Alrm Det
ON: VFD detects that the internal cooling fan has failed
OFF: Normal operation
37 Maintenance
ON: Maintenance Timer U01-52
≥
C12-05
OFF: Normal operation or the Maintenance Timer U01-52 < C12-05
38 Spd Lim @ T Cont
ON: Speed Limit has been reached while using Torque Control
OFF: Speed Limit has not been reached when using Torque Control
39 Drive Enable
ON: VFD is Enabled
OFF: VFD Enable (H01-xx = 55) is not active
3B Watt-hour Pulse
ON: Watt-hour time is reached (based on H02-06), the contact will close for 200 ms
OFF: Normal operation
3D Fault or Alarm
ON: Fault or Alarm condition is detected
OFF: Normal operation
3E Overspeed
ON: Overspeed condition is detected
OFF: Normal operation
3F Klixon
ON: Klixon alarm is detected (H01-xx = 56 or 57 is active)
OFF: Normal operation
40 through FF
Flt Annunciate
ON: Specific fault condition detected (
see Section 5.6.3.1 on page 150
)
OFF: Normal operation
102 through 1FF**
Settings 2 through FF with inverse output.