Load management program
76 / 156
Charge Point information
ID:
Unique ID of the Charge Point. In ISO 15118-2, the ID of the Charge
Point is called EVSE-ID. According to ISO 15118-2, it is a globally unique
identifier containing an octet string. In communication with the Electric
Vehicle, the Charge Point ID will be concatenated with the Socket ID to
receive the EVSE-ID.
[default value: Charge Point ID]
Name:
Human-readable name of the Charge Point for presentation purposes.
[default value: Charge Point ID]
Metering
Publishes meter values?
Decides how intermediate meter reading will be handled.
Display values:
No:
Intermediate meter readings will neither be stored in the Charging
Transaction nor written to a log file.
Most recent:
The most recent intermediate meter reading will be stored at the
Charging Transaction, but no log file entry will be written.
Full log:
The most recent intermediate meter reading will be stored at the
Charging Transaction and written to the log file.
Metering period:
Duration in seconds between two consecutive intermediate meter read-
ings. The period may not be smaller than 5 seconds.
Recommendation: Due to the high data amount, do not enter a short me-
tering period for a long time.
Meter collection type:
Type of collection of meter readings for export.
Display values:
ClockAligned:
Meter readings will be generated for Sockets or the Charge Point.
They will be collected in evenly spaced intervals starting from mid-
night.
Sampled:
Meter readings will be generated for Charging sessions. They will be
collected at the start and end of the Charging session as well as in
evenly spaced intervals starting from the start of the Charging ses-
sion.
Both:
Both clock-aligned and sampled Meter readings will be collected.
Collection interval clock
aligned:
Size (in seconds) of the clock-aligned data interval. This is the size of the
set of evenly spaced aggregation intervals per day, starting at 00:00:00
(midnight). Optional. Must be populated, if Meter Collection Type =
ClockAligned or Both.
Collection interval session
aligned:
Interval (in seconds) between sampling of metering data, intended to be
exported. Sampling starts at the begin of the Charging session. Optional.
Must be populated, if Meter Collection Type = Sampled or Both.