Hardware installation
22 / 156
SETTING THE AMPERAGE (DSW1) (*1)
Current
D1.6
D1.7
D1.8
Figure
10A
OFF
OFF
OFF
13A
ON
OFF
OFF
16A
OFF
ON
OFF
20A
ON
ON
OFF
25A
OFF
OFF
ON
32A
ON
OFF
ON
(*1)
Preadjusted maximum current value for the EV charger (control pilot duty cycle).
STANDARD MODE + DHCP (NO ADDRESSING)
DSW2.1 to DSW2.4=OFF / DSW2.6=OFF
The charging procedure in
STANDARD
mode is
carried out automatically by the charging station
without higher-ranking control system.
The charging station attempts to obtain an IP
address via
DHCP
server, if needed.
This also corresponds to the basic settings for
charging stations without network connection.