Art. No. DS 4092 TS
disabling function
Switching object 1.1
OFF
TOGGLE
this object at the beginning of the
disabling. "TOGGLE" switches over the
current object value.
Behaviour at the end of
the disabling function
Switching object 1.1
No reaction
ON
OFF
Transmit current input
status
With an active disable, the first switching
object is disabled. This parameter
specifies the command transmitted via
this object at the end of the disabling.
"TOGGLE" switches over the current
object value. In the "Transmit current
input status" setting, the device
evaluates the current static signal status
of the input and, according to this,
transmits the appropriately configured
telegram to the bus (contact closed at
the input = telegram as with rising edge;
contact open at input = telegram as with
falling edge).
Disabling function
switching object 1.2
disabled
enabled
The extension inputs can be separately
disabled via the bus using 1-bit objects.
With the "Switching" function, it is
possible to disable the two switching
objects of an input independently of
each other. With an active disabling
function, signal edges at the input are
ignored by the device related to the
affected objects.
This parameter enables the disabling
function of the second communication
object.
Polarity of the disabling
object
disable = 1 /
enable = 0
disable = 0 /
enable = 1
This parameter defines the polarity of
the disabling object.
Behaviour at the
beginning of the
disabling function
Switching object 1.2
No reaction
ON
OFF
TOGGLE
With an active disable, the second
switching object is disabled. This
parameter specifies the command
transmitted via this object at the
beginning of the disabling. "TOGGLE"
switches over the current object value.
Behaviour at the end of
the disabling function
Switching object 1.2
No reaction
ON
OFF
Transmit current input
status
With an active disable, the second
switching object is disabled. This
parameter specifies the command
transmitted via this object at the end of
the disabling. "TOGGLE" switches over
the current object value. In the "Transmit
current input status" setting, the device
evaluates the current static signal status
of the input and, according to this,
Page 135 of 143
Software "Rotary sensor with extensions 10FE1x"
Parameters