Art. No. DS 4092 TS
50 %
100 %
Especially with smaller dimming levels it
is advisable for the push button sensor
to repeat the dimming telegrams
automatically (see "telegram repetition").
Transmit stop telegram?
yes
no
On "Yes" the push-button transmits a
telegram for stopping the dimming
process when the rocker is released.
When the push-button transmits
telegrams for dimming in small
increments, the stop telegram is
generally not needed.
Telegram
repeat?
yes
no
This parameter can be used to activate
telegram repetition for dimming. The
push-button will then transmit the
relative dimming telegrams (in the
programmed step width) until it is
released.
Time between two
telegrams
200 ms
300 ms
400 ms
500 ms
750 ms
1 sec
2 sec
This parameter defines the interval at
which the dimming telegrams are
automatically repeated in the telegram
repetition mode.
This parameter is visible only if
"Telegram repetition = yes"!
The following parameters are visible for the function "Venetian Blind"...
Command on pressing
the button
no reaction
DOWN
UP
TOGGLE
This parameter defines the running
direction of a drive after a button-press.
If the setting is "TOGGLE", the direction
is changed after each long time
command. If several push buttons are to
control the same drive, the long time
objects of the push buttons must be
interlinked for a correct change of the
running direction.
Operation concept
short – long – short
long – short
short – long
long – short or short
For Venetian blind control, four different
operation concepts can be selected. For
these concepts, the ETS shows further
parameters.
Time between short-
time and long-time
1...
4
...3000
This parameter sets the time after which
the long-time operation will be evaluated
on pressing the button.
Page 100 of 143
Software "Rotary sensor with extensions 10FE1x"
Parameters