Art. No. DS 4092 TS
4.2.5.2 Extension inputs parameter
Description
Values
Comment
h
Extension inputs (E)
Delay after bus voltage
return
Minutes (0...59)
0
...59
It is possible to specify separately for
each input whether a reaction should
take place after a device reset (bus
voltage return or ETS programming
operation). This means that a defined
telegram can be transmitted to the bus
according to the input signal or with
forced control. The delay time for the
extension inputs configurable at this
point must have elapsed fully by the
time the set reaction is executed. Within
the delay, any pending edges or signals
at the inputs are not evaluated and are
ignored.
Minute setting of the delay time for the
extension inputs.
Seconds (0...59)
0...
17
…59
Second setting of the delay time for the
extension inputs.
Debounce time
(10...120 ms)
10...
30
...120
This parameter specifies the time for
software debounce for all the extension
inputs. A signal edge at the input is
evaluated after a delay according to the
time set here.
Telegram rate
limit
disabled
enabled
Here it is possible to configure a general
telegram rate limit. If the telegram rate
limit is enabled, no more telegrams are
transmitted to the bus in 17 seconds
(permanently defined, cyclical time
interval) than is specified by the
parameter "Telegrams per 17 s". This
avoids fast edge changes at the inputs
causing an inpermissibly high bus load.
Telegrams per 17 s
30
, 60, 100, 127
Setting the telegram rate (telegrams in
17 s) for the telegram rate limit.
Only visible on "Telegram rate limit =
enabled".
h
Ex - General (x = 1, 2, 3)
Function
No function
Switching
Dimming
Venetian blind
Value transmitter
The basic function of the appropriate
extension input is defined here.
In the "No function" setting, the
extension input is deactivated.
The following parameters are visible for the function "Switching"...
Page 126 of 143
Software "Rotary sensor with extensions 10FE1x"
Parameters