Art. No. DS 4092 TS
Configuring the reaction for the rotary knob during disabling
Regardless of the behaviour at the beginning or end of disabling, the rotary knob can be
influenced separately during disabling.
The disabling function must have been enabled in advance.
o
Set the parameter "Behaviour of the rotary knob during disabling" to "no function".
The rotary knob is completely disabled during disabling. An operation has no effect. The
buzzer then no longer signals any operations either while it is configured to "button-press
display".
o
Set the parameter "Behaviour of the rotary knob during disabling" to "as disabling function
rotary knob".
The rotary knob behaves as specified by the configuration of the disabling function. The
telegrams are transmitted to the bus via the communication objects of the disabling
function. The buzzer then no longer signals any operations either while it is configured to
"button-press display".
i
If a rotary knob operation is taking place at the time of activation / deactivation of a
disabling function, the associated operating function is aborted immediately.
Page 77 of 143
Software "Rotary sensor with extensions 10FE1x"
Functional description