Goodrive20-UL Series VFD
Function parameters
-72-
Function
code
Name
Description
Default Modify
state at
previous 2
faults
P08 group Enhanced functions
Function
code
Name
Description
Default Modify
P08.00
ACC time
2
Refer to P00.11 and P00.12 for detailed
definition.
Goodrive20-UL series define four groups of
ACC/DEC time which can be selected by P5
group. The first group of ACC/DEC time is the
factory default one.
Setting range: 0.0
–3600.0s
Depend
on model
○
P08.01
DEC time
2
Depend
on model
○
P08.02
ACC time
3
Depend
on model
○
P08.03
DEC time
3
Depend
on model
○
P08.04
ACC time
4
Depend
on model
○
P08.05
DEC time
4
Depend
on model
○
P08.06
Jogging
running
frequency
This parameter is used to define the reference
frequency during jogging.
Setting range: 0.00Hz
–P00.03 (Max. output
frequency)
5.00Hz
○
P08.07
Jogging
running
ACC time
The jogging ACC time means the time needed if
the VFD runs from 0Hz to the Max. Frequency.
The jogging DEC time means the time needed if
the VFD goes from the Max. Frequency
(P00.03) to 0Hz.
Setting range: 0.0
–3600.0s
Depend
on model
○
P08.08
Jogging
running
DEC time
Depend
on model
○
P08.09
Jumping
frequency
1
When the set frequency is in the range of
jumping frequency, the VFD will run at the edge
of the jumping frequency.
The VFD can avoid the mechanical resonance
point by setting the jumping frequency. The VFD
can set three jumping frequency. But this
function will be invalid if all jumping points are 0.
0.00Hz
○
P08.10
Jumping
frequency
range 1
0.00Hz
○
P08.11
Jumping
frequency
2
0.00Hz
○