Goodrive20-UL Series VFD
Function parameters
-47-
Function
code
Name
Description
Default Modify
keypad
defined
value
P03.18
Upper-limit
setting of
electromoti
on torque
This function code is used to select the
electromotion and braking torque upper-limit
setting source selection.
0: Keypad setting upper-limit frequency
(P03.20 sets P03.18 and P03.21 sets P03.19)
1: Analog AI1 setting upper-limit torque
2: Analog AI2 setting upper-limit torque
3: Analog AI3 setting upper-limit torque
4: Pulse frequency HDI setting upper-limit
torque
5: Modbus communication setting upper-limit
torque
6
–8: Reserved
Note:
Setting mode 1
–8, 100% corresponds to
three times of the motor current.
0
○
P03.19
Upper-limit
setting of
braking
torque
0
○
P03.20
Electromoti
on
torque
upper-limit
keypad
setting
The function code is used to set the limit of the
torque.
Setting range: 0.0
–300.0% (motor rated
current)
180.0%
○
P03.21
Braking
torque
upper-limit
keypad
setting
180.0%
○
P03.22
Weakening
coefficient
in constant
power zone
The usage of motor in weakening control.
Function code P03.22 and P03.23 are effective
at constant power. The motor will enter into the
weakening state when the motor runs at rated
speed. Change the weakening curve by
modifying the weakening control coefficient.
The bigger the weakening control coefficient is,
the steeper the weak curve is.
Setting range of P03.22: 0.1
–2.0
Setting range of P03.23: 10%
–100%
0.3
○
P03.23
The lowest
weakening
point in
constant
power zone
20%
○
Summary of Contents for GD20-0R4G-2-UL
Page 1: ......