Goodrive20-UL Series VFD
Function parameters
-92-
Function
code
Name
Description
Default Modify
2: current limit is invalid during constant
speed
Setting range of P11.05: 0x00
–0x12
Setting range of P11.06: 50.0
–200.0%
(relative to the percentage of rated current of
the VFD)
Setting range of P11.07: 0.00
–50.00Hz/s
P11.08
Overload
pre-alarm of
the motor/
VFD
Overload pre-alarm signal will be outputted if
the output current of the VFD or motor is
higher than overload pre-alarm detection
level (P11.09), and the duration exceeds
overload pre-alarm detection time (P11.10).
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time t
Pre-alarm time t
Setting range of P11.08:
The function code is used to enable and
define the overload pre-alarm of the
VFD/motor.
Setting range: 0x0000
–0x1132
Ones place:
0: Motor overload/underload pre-alarm,
relative to rated motor current;
1: VFD overload/underload pre-alarm,
relative to rated VFD current.
2: Motor output torque overload/underload
pre-alarm, relative to rated motor torque
Tens place:
0: The VFD continues running after
overload/underload alarm;
1: The VFD continues running after
0x0000
○
P11.09
Overload
pre-alarm
detection
level
150%
○
P11.10
Overload
pre-alarm
detection
time
1.0s
○
Summary of Contents for GD20-0R4G-2-UL
Page 1: ......