Goodrive20-UL Series VFD
Fault tracking
-107-
Fault
code
Fault type
Possible cause
Solutions
OUt3
[3] Inverter unit W
phase protection
interference;
The connection of the
driving wires is not
good;
Grounding is not
properly.
wires;
Inspect external
equipment and
eliminate interference.
OC1
[4] Overcurrent
during acceleration
The acceleration or
deceleration is too
fast.
The voltage of the grid
is too low.
The power of the VFD
is too low.
The load transients or
is abnormal.
The grounding is
short circuited or the
output is phase loss.
There
is
strong
external interference.
The overvoltage stall
protection is not open.
Increase
the
ACC
time.
Check
the
input
power.
Select the VFD with a
larger power.
Check if the load is
short circuited (the
grounding short
circuited or the wire
short circuited) or the
rotation is not smooth.
Check the output
configuration.
Check if there is
strong interference.
Check the setting of
relative function
codes.
OC2
[5] Overcurrent
during deceleration
OC3
[6] Overcurrent
during constant
speed running
OV1
[7] Overvoltage
during acceleration
The input voltage is
abnormal.
There is large energy
feedback.
No braking
components.
Braking energy is not
open.
Check the input power
Check if the DEC time
of the load is too short
or the VFD starts
during the rotation of
the motor or it needs
to increase the energy
consumption
components.
Install the braking
components.
Check the setting of
relative function
codes.
OV2
[8] Overvoltage
during deceleration
OV3
[9] Overvoltage
during constant
speed running