Goodrive20-UL Series VFD
Function parameters
-39-
Function
code
Name
Description
Default Modify
P01.17
Detection
time of the
feedback
speed
When P01.16=1, the actual output frequency of
the VFD is less than or equal to P01.15 and is
detected during the time set by P01.17, the VFD
will stop; otherwise, the VFD stops in the time
set by P01.24.
T
Stop
speed
A
Ramp
reference
frequency
Output frequency
Frequency
P01.24 P01.17
B
C
Running A
Running B
Running C
Setting range: 0.00
–100.00s (valid only when
P01.16=1)
0.50s
◎
P01.18
Terminal
running
protection
selection
when
powering
on
When the running command channel is the
terminal control, the system will detect the state
of the running terminal during powering on.
0: The terminal running command is invalid
when powering on. Even the running command
is detected to be valid during powering on, the
VFD won't run and the system keeps in the
protection state until the running command is
canceled and enabled again.
1: The terminal running command is valid when
powering on. If the running command is
detected to be valid during powering on, the
system will start the VFD automatically after the
initialization.
Note:
This function should be selected with
cautions, or serious result may follow.
0
○
P01.19
Action
selected
when
running
frequency
less than
frequency
lower limit
0x00
–0x12
Ones place:
0: Run at the frequency lower limit
1: Stop
2: Sleep
Tens place: Stop mode
0: Coast to stop
1: Decelerate to stop
0x00
◎
Summary of Contents for GD20-0R4G-2-UL
Page 1: ......