Goodrive20-UL Series VFD
Function parameters
-97-
Function
code
Name
Description
Default Modify
upper monitor. The communication efficiency
can be increased in this mode.
Tens place: Communication encryption
0: Disabled
1: Enabled
Hundreds
place:
Self-define
the
communication command address
0: Disabled
1: Enabled
P14.07
Self-defined
address of
the running
command
0x0000
–0xffff
0x1000
○
P14.08
Self-defined
address of
frequency
setting
0x0000
–0xffff
0x2000
○
P17 group Status viewing
Function
code
Name
Description
Default Modify
P17.00
Setting
frequency
Display current set frequency of the VFD
Range: 0.00Hz
–P00.03
●
P17.01
Output
frequency
Display current output frequency of the VFD
Range: 0.00Hz
–P00.03
●
P17.02
Ramp
reference
frequency
Display current ramp
reference frequency of
the VFD
Range: 0.00Hz
–P00.03
●
P17.03
Output
voltage
Display current output voltage of the VFD
Range: 0
–1200V
●
P17.04
Output
current
Display current output current of the VFD
Range: 0.0
–5000.0A
●
P17.05
Motor speed
Display the rotation speed of the motor.
Range: 0
–65535RPM
●
P17.06
Torque
current
Display current torque current of the VFD
Range: 0.0
–5000.0A
●
P17.07
Magnetized
current
Display current magnetized current of the
VFD
●
Summary of Contents for GD20-0R4G-2-UL
Page 1: ......