Goodrive20-UL Series VFD
Function parameters
-27-
Chapter 5 Function parameters
The function parameters of Goodrive20-UL series VFDs have been divided into 30 groups
(P00
–P29) according to the function, of which P18–P28 are reserved. Each function group
contains certain function codes. A three-level menu style is applied to function codes. For
example, "P08.08" indicates the 8th function code in the P8 group. The P29 group consist of
factory function parameters, which are user inaccessible.
The function group numbers correspond to the level-1 menus, the function codes correspond
to the level-2 menus, and the function parameters correspond to the level-3 menus.
1. The content of the function code table is as follows:
Column 1 "Function code": Code of the function group and parameter.
Column 2 "Name": Full name of the function parameter.
Column 3 "Description": Detailed description of the function parameter.
Column 4 "Default": Initial value set in factory.
Column 5 "Modify": Whether the function parameter can be modified, and conditions for the
modification.
"
○
" indicates that the value of the parameter can be modified when the VFD is in the stop or
running state.
"
◎
" indicates that the value of the parameter cannot be modified when the VFD is in the
running state.
"
●
" indicates that the value of the parameter is detected and recorded, and cannot be
modified.
P00 group Basic functions
Function
code
Name
Description
Default Modify
P00.00
Speed
control
mode
0: SVC 0
No need to install encoders. Suitable in
applications which need low frequency, big
torque for high accuracy of rotating speed and
torque control. Relative to mode 1, it is more
suitable for the applications which need small
power.
1: SVC 1
2
◎
Summary of Contents for GD20-0R4G-2-UL
Page 1: ......