Goodrive20-UL Series VFD
Optional peripheral accessories
-144-
C.2 Power supply
Ensure that the voltage class of the VFD is consistent with that of the grid.
C.3 Cables
C.3.1 Power cables
The sizes of the input power cables and motor cables must meet the local regulation. Use
75°C CU wire only.
Note:
If the conductivity of the shielding layer of the motor cables cannot meet the
requirements, separate PE conductors must be used.
Required wire torque, type and range for field input and output terminals listed below:
Model No.
Terminal Type
Required
Torque
(in-lbs)
Wire
Range
Wire
Connector
(##)
GD20-0R4G-S12
Input and Output
Terminal
4.4@@
12 AWG
Required
GD20-0R7G-S12
GD20-1R1G-S12
GD20-0R4G-S2-UL
Input and Output
Terminal
4.4 or 8.8
@@
14 AWG
Optional
GD20-0R7G-S2-UL
GD20-1R5G-S2-UL
Input and Output
Terminal
4.4 or 8.8
@@
12 AWG
Required
GD20-2R2G-S2-UL
Input and Output
Terminal
4.4@@
12 AWG
Required
GD20-0R4G-2-UL
Input and Output
Terminal
7
14 AWG
Optional
GD20-0R7G-2-UL
GD20-0R7G-4-UL
GD20-1R5G-4-UL
GD20-2R2G-4-UL
All models
Control Terminal
Block
4.5
26-14
(Str/Sol)
AWG
Optional
@@: See marking on product for tightening torque detail.
##: UL listed wire connector shall be used.
The models GD20-0R4G-S2-UL/GD20-0R7G-S2-UL/GD20-1R5G-S2-UL use terminal blocks
of ANYTEK and DEGSON, and the tightening torque must be 8.8 in-lb (ANYTEK) and 4.4 in-lb
(DEGSON) or equivalent.
Summary of Contents for GD20-0R4G-2-UL
Page 1: ......