Goodrive20-UL Series VFD
Fault tracking
-109-
Fault
code
Fault type
Possible cause
Solutions
OH1
[15] Rectifier
module overheat
Air duct jam or fan
damage.
Ambient temperature
is too high.
The time of overload
running is too long.
Dredge the vent duct
or replace the fan.
Low the ambient
temperature.
OH2
[16] Inverter module
overheat
EF
[17] External fault
SI external fault input
terminals action.
Check the external
device input.
CE
[18] 485
communication
fault
The baud rate setting
is incorrect.
Fault occurs to the
communication
wiring.
The communication
address is wrong.
There is strong
interference to the
communication.
Set proper baud rate.
Check the
communication
connection
distribution.
Set proper
communication
address.
Chang or replace the
connection
distribution or improve
the anti-interference
capability.
ItE
[19] Current
detection fault
The control panel
connector is in poor
contact;
An exception occurs
on the magnifying
circuit.
Check the connector
and re-plug.
Change the main
control panel.
tE
[20] Motor
autotuning fault
The motor capacity
does not comply with
the VFD capability.
The rated parameter
of the motor does not
set correctly.
The offset between
the parameters from
autotune and the
Change the VFD
mode.
Set the rated
parameter according
to the motor name
plate.
Empty the motor load.
Check the motor
connection and set
Summary of Contents for GD20-0R4G-2-UL