Goodrive20-UL Series VFD
Function parameters
-51-
Function
code
Name
Description
Default Modify
P04.12
Vibration
control
threshold
30.00 Hz
○
P04.26
Energy-sa
ving
operation
selection
0: No operation
1: Automatic energy-saving operation
Motor on the light load conditions, automatically
adjusts the output voltage to save energy
0
◎
P04.27
Voltage
Setting
channel
Select the output setting channel at V/F curve
separation.
0: Keypad setting voltage: the output voltage is
determined by P04.28.
1: AI1 setting voltage
2: AI2 setting voltage
3: AI3 setting voltage
4: HDI setting voltage
5: Multi-step speed setting voltage;
6: PID setting voltage;
7: Modbus communication setting voltage;
8
–10: Reversed
Note:
100% corresponds to the rated voltage of
the motor.
0
○
P04.28
Keypad
setting
voltage
The function code is the voltage digital set value
when the voltage setting channel is selected as
"keypad selection".
Setting range: 0.0%
–100.0%
100.0%
○
P04.29
Voltage
increasing
time
Voltage increasing time is the time when the
VFD accelerates from the output minimum
voltage to the output maximum voltage.
Voltage decreasing time is the time when the
VFD decelerates from the output maximum
voltage to the output minimum voltage.
Setting range: 0.0
–3600.0s
5.0s
○
P04.30
Voltage
decreasing
time
5.0s
○
P04.31
Output
maximum
voltage
Set the upper and low limit of the output voltage.
Setting range of P04.31: P04.32
–100.0%
(the rated voltage of the motor)
Setting range of P04.32: 0.0%
– P04.31
(the rated voltage of the motor)
100.0%
◎
P04.32
Output
minimum
voltage
0.0%
◎