Goodrive20-UL Series VFD
Function parameters
-77-
Function
code
Name
Description
Default Modify
P08.38
Energy
braking
threshold
voltage
After setting the original bus voltage of energy
braking, you can adjust the voltage to
implement load braking. The factory changes
with the voltage level.
Setting range: 200.0
–2000.0V
In order to prevent customers set the value is
too large, it is recommended setting range:
Voltage
220V
460V
Range
375
–400V
715
–780V
220V
voltage:
380.0V
○
460V
voltage:
740.0V
P08.39
Cooling
fan
running
mode
0: Rated running mode
1: The fan keeps running after being powered
on
2: The fan runs when the VFD ramp frequency
is no less than 0Hz, and the VFD output current
is no less than 10% of the VFD rated current. If
the VFD ramp frequency is 0Hz and the VFD
output current is less than 10% of the VFD rated
current or the VFD stops running, the fan stops
running whithin 1 minute.
0
○
P08.40
PWM
selection
0x00
–0x21
Ones place: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
Tens place: low-speed carrier frequency limit
mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k
at low speed
1: Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k
at low speed
2: No limit
0x01
◎
P08.41
Over
commissio
n selection
Ones place:
0: Invalid
1: Valid
Tens place: (for factory commissioning)
0: Light overcommission; in zone 1
1: Heavy overcommission; in zone 2
0x00
◎