iBAT 2.0-CIM01C2
User Manual
5 System Commissioning
Issue 07 (2019-01-02)
Copyright © Huawei Technologies Co., Ltd.
44
Parameter
Description
Battery N line
Set whether there is a battery N wire according to the actual
situation.
Single batt. group
number of HALL
Indicates the number of Hall effect sensors connected to a single
battery string.
Single batt. capacity Specifies the capacity of each battery that is connected in the battery
string in series.
Batt. installation
time
Time when the battery is installed for the first time. Does not need
to be reset when part of batteries are replaced.
iBAT number of
iBOX
Indicates the total number of iBATs managed by the iBOX.
Number of battery
strings
Indicates the total number of battery strings managed by the iBOX.
Batt. string No.
Sets the battery string numbers of the iBOXs connected in parallel
to unique ones when multiple iBOXs are connected in parallel.
Parallel
Communication
Configuration
This parameter needs to be set when multiple iBOXs are connected
in parallel and does not need to be set when there is only one iBOX.
Set
Whether the iBOX communicates directly with the NetEco
to
Yes
, and set
Number of iBOX configured under each UPS
.
Configure IP addresses for multiple iBOXs.
Modbus Config
Set ModbusTCP encryption and ModbusTCP authentication, which
are consistent with Connection Mode on the NetEco.
HALL Rerverse
Config
If the Hall effect sensor is reversely installed, you can set reverse
connection to correct it.
Basic Information
If a BCB box is configured, set
BCB configuration
to
Done
and
Batt. abnormal BCB trip
to
Enable
.
Time
Set the local time zone, date, and time.
IP Address
Set the IP address, subnet mask, and default gateway of the iBOX.
Set this parameter based on the IP address assigned by the
administrator.
b.
On the iBOX WebUI homepage, choose
System Settings
>
Battery Curve
and set
the battery curve for each battery string.
c.
On the
Battery Curve
page, select the battery string to be set, set
Battery Brand
and
Format
, click
Filter
>
Submit
.