Parameter
Description
Batt. string No.
The serial number of each battery string. Under the same CIM, the
battery string numbers must be unique.
V291B028
a.
On the iBOX WebUI home page, choose
System Settings
>
Running Parameter
,
and set
Parallel Configuration
.
b.
On the iBOX WebUI home page, choose
System Settings
>
Batt. String Config
,
and set
Batt. String Config
.
Parameter
Description
Parallel
Configuration
This parameter needs to be set when multiple iBOXs are connected
in parallel and does not need to be set when there is only one iBOX.
Set
Parallel Configuration
to
Parallel
, and set
iBOX parallel qty.
.
Configure IP addresses for multiple CIMs.
Current acquisition
source
The actual specifications of the Hall effect sensor prevail.
Battery N line
Set whether there is a battery N wire according to the actual
situation.
Multi-Hall cur.
setting
The number of positive or negative Hall effect sensors in a single
battery string and should be greater than or equal to 1.
Total battery
capacity
One iBOX: Capacity of one battery string x Number of battery
strings connected in parallel.
N iBOXs connected in parallel: Capacity of one battery string x
(Number of battery strings managed by iBOX 1 + … + Number
of battery strings managed by iBOX N).
Batt. installation
time
Time when the battery is installed for the first time. Does not need to
be reset when part of batteries are replaced.
iBAT Number of
iBOX
Indicates the total number of iBATs managed by the iBOX.
Number of battery
strings
The number of battery strings managed by the iBOX.
Batt. string No.
The serial number of each battery string. Under the same iBOX, the
battery string numbers must be unique.
V296B019
a.
On the iBOX WebUI, choose
System Settings
, and set
Batt. String Config
,
Running Parameter
,
Time
and
IP Address
.
Parameter
Description
Current acquisition
source
The actual specifications of the Hall effect sensor prevail.