iBAT 2.0-CIM01C2
User Manual
2 Overview
Issue 07 (2019-01-02)
Copyright © Huawei Technologies Co., Ltd.
14
Blinking intermittently at super short intervals means an indicator blinks at super short intervals for
0.5s and then remains off for 0.5s.
Networking Switch
Table 2-11
Networking switch description
Name
Definition
Function
Button pressing
Press the button for
less than 1s.
CIM blinking function
Button pressing
Press and hold the
button for more than
1s but less than 5s.
Creates a network if no network has
been created. Switches between network
organization and data transmission if a
network has been created.
Button holding down
Press and hold the
button for more than
10s but less than 20s.
Clears the current network (including
the network parameters of all the online
BIMs).
Default Button
Table 2-12
Default button description
Name
Definition
Function
Default button
Press and hold the
button for more than
10s but less than 20s.
Reset to the default IP address
(192.168.0.10).
2.2 BIM
The BIM (BIM01C3) is a battery monitoring module that supports 12 V power input and
monitors the voltages, internal resistances, and pole temperatures of batteries.
The BIM (BIM02C1) is a battery monitoring module that supports 2 V power input and
monitors the voltages, internal resistances, and pole temperatures of batteries.
Features
Monitors the voltages, internal resistances, and pole temperatures of batteries.
Uploads battery data to CIM through wireless communication.
Has the hibernation function: