5 System Commissioning
Issue 07 (2019-01-02)
Copyright © Huawei Technologies Co., Ltd.
46
Parameters
Description
Remarks
Battery string No.
The serial number of each
battery string. Set this
parameter based on the
planned codes for iBOXs
and battery strings. The
Battery string No.
are
unique for a same UPS.
Set according to the
customer plan.
BCB tripping upon battery
abnormal
If the BCB box is
configured, set
BCB
tripping upon battery
abnormal
to
Enable
.
N/A
If multiple iBOXs are connected, commission the iBOX one by one in the same way. Otherwise,
networking may be in disorder.
----End
5.3 Setting Parameters on the UPS Monitoring Screen
(UPS Scenario)
Context
The UPS software version UPS5000 V100R003C01SPC408 is used for reference.
On the WebUI and LCD of some UPSs, iBOX is named CIM, and iBAT is named BIM.
Procedure
Step 1
Set UPS parameters.
UPS LCD
a.
On the UPS LCD home screen, choose
System Info
>
Settings
>
Battery Settings
,
and set
Number of battery strings
.
b.
On the UPS LCD home screen, choose
System Info
>
Settings
>
iBOX Settings
,
and set
Basic Param.
,
Advanced Param.
, and
Batt. String Config
.