5 System Commissioning
Issue 07 (2019-01-02)
Copyright © Huawei Technologies Co., Ltd.
48
Figure 5-8
Batt. String Config
Item
Description
Number of battery
strings
Specifies the number of battery strings connected in parallel.
Number of iBOXs
The number of iBOXs connected to UPS.
iBOX start address
Communication address of the iBOX when the UPS queries
iBOX data.
iBOX number of
iBATs
Specifies the number of iBATs managed by the iBOX.
iBOX logical start addr
Specifies the communication address when the northbound
device queries iBOX data. When connecting the UPS to the
network management system, do not set
iBOX logical start
addr
to
0
or a value same as the UPS
Address
.
Current source
Specifications of the Hall effect sensor used to detect iBOX
current.
Batt. abnormal BCB
trip
If the BCB box is configured, set
Batt. abnormal BCB trip
to
Enable
.
Multi-Hall cur. setting
Multi-Hall cur. setting is equal to the number of Hall effect
sensors at the positive or negative terminal of a battery string
(Multi-Hall cur. setting ≥ 1).
iBOX No.
Set this parameter based on the planned codes for iBOXs.
UPS WebUI
a.
On the UPS WebUI homepage, choose
Param. Settings
>
Battery Setting
, and set
Number of battery strings
.
b.
On the UPS WebUI homepage, choose
iBOX Settings
, and set
Basic Param.
,
Advanced Param.
, and
Batt. String Config
.