iBAT 2.0-CIM01C2
User Manual
A Technical Specifications
Issue 07 (2019-01-02)
Copyright © Huawei Technologies Co., Ltd.
70
A
Technical Specifications
Table A-1
Environmental requirements
Item
CIM
BIM
Operating
temperature
–20°C to +65°C
–20°C to +65°C
Storage
temperature
–40°C to +80°C
–40°C to +70°C
Relative
humidity
5%–95% RH
5%–95% RH
Altitude
0–4000 m
At 2000–4000 m, the product
works at derated mode, and the
operating temperature decreases by
1°C for each additional 200 m.
0–4000 m
At 2000–4000 m, the product
works at derated mode, and the
operating temperature decreases by
1°C for each additional 200 m.
Table A-2
CIM EMC specifications
Item
Specifications
Conducted
emission (CE)
EN55032
DC port: Class A
Radiated emission
(RE)
EN55032, Class A
Electrostatic
discharge (ESD)
IEC61000-4-2
Enclosure touchable by hand during normal operations: contact
discharge ±6 kV; air discharge ±8 kV, criterion B (power-on before
testing)
Electrical fast
transient (EFT)
IEC61000-4-4
DC port: ±2 kV, criterion B
Signal port: ±1 kV, criterion B