Access Controller
·
User Manual
89
The Card Swiping Times should be larger than 0 and smaller than the added card
quantity in the card group.
The upper limit of Card Swiping Times is 16.
6)
Click
OK
to save the settings.
5.
Click
Save
to save and take effect of the new settings.
Notes:
For each access control point (door), up to four authentication groups can be added.
For the authentication group which certificate type is
Local Authentication
, up to 8 card
groups can be added to the authentication group.
For the authentication group which certificate type is
Local Authentication and Super
Password
or
Local Authentication and Remotely Open Door
, up to 7 card groups can be
added to the authentication group.
7.8.4
Open Door with First Card
Purpose:
You can set multiple first cards for one access control point. After the first card swiping, it allows
multiple persons access the door or other authentication actions. The first card mode contains
Remain Open with First Card, Disable Remain Open with First Card, and First Card Authorization.
Remain Open with First Card:
The door remains open for the configured time duration after the
first card swiping until the remain open duration ends.
First Card Authorization:
All authentications, except for the authentications of super card, duress
card, and duress code, are allowed only after the first card authorization.
Steps:
1.
Click
Open Door with First Card
tab to enter the following interface.
2.
Select an access control device from the list on the left.
3.
Select the first card mode in the drop-down list for the access control point.
4.
(Optional) If you select Remain Open with First Card, you should set remain open duration.