Chapter 5 Automatic Operation
101
Ⅲ
Function
[
Classification
]
Output signal
[
Function
]
The signal reports PLC of the state of single block signal.
[
Operation
]
The signal is set to 1 as follows:
――
When the single block signal SBK is set to1.
The signal is set to 0 as follows:
――
When the single block signal SBK is set to 0.
Note:
Operations in thread cutting.
When the SBK signal becomes 1 during the thread cutting and the thread cutting code is
executed, the operation stops at the 1
st
non thread cutting block.
Signal address
5.4 Optional Block Skip
General
When a slash followed by a number is specified at the head of a block, and optional
block skip signal BDT is set to 1 during automatic operation, the block is ignored
.
Signal
Skip optional block signal
BDT
(
G044#0
)
[
Classification
]
Input signal
[
Function
]
Select whether a block with “/” is neglected.
[
Operation
]
During automatic operation, when BDT is 1, the block with “/” is
neglected.
The program is normally executed when BDT is 0.
Optional block skip check signal
MBDT
(
F004#0
)
[
Classification
]
Output signal
[
Function
]
The signal reports PLC of the state of skip optional block BDT.
Signal address
SBK
G046
#
7
#
6
#
5
#
4
#
3
#
2
#
1
#
0
MSBK
F004
BDT
G044
#
7
#6
#
5
#
4
#
3
#
2
#1
#
0
MBDT
F004