Unit Control
[Notes]
●When ―
Remote sensor
‖ is set to ―
With
‖, this setting can be set to ―
T-water out
‖ or ―
T-room
‖. When
―
Remote sensor
‖ is set to ―
Without
‖, this setting can only be set to ―
T-water out
‖.
● This setting will be memorized upon power failure.
3.2.4.2 2-Way valve
[Operation Instructions]
★
At the commissioning parameter setting
page, by touching ―
Cool 2-Way valve
‖ or ―
Heat 2-Way
valve
‖, the control panel will access to the corresponding setting page.
[Notes]
●Under ―
Cool
‖, or ―
Cool + Hot water
‖ mode, ―
Cool 2-Way valve
‖ will decide the status of the 2-way
valve; while under ―
Heat
‖ or ―
Heat + Hot water
‖, ―
Heat 2-Way valve
‖ will decide the status of the 2-way
valve.
●It will be memorized upon power failure.
3.2.4.3 Solar Setting
[Operation Instructions]
★
1. At the commissioning parameter setting page, by touching ―
Solar setting
‖, the control panel will
access to its submenu page.
★
2. At the submenu page, ―
Solar setting
‖ can be set to ―
With
‖ or ―
Without
‖.
★
3. At the submenu page, the ―
Solar heater
‖ can be set to ―
On
‖ or ―
Off
‖.
Solar Setting
[Notes]
●This setting can be done no matter if the unit is turned on or off.
●This setting is allowed only when the water tank is available. When the water tank is unavailable, this
setting will be reserved.
●It will be memorized upon power failure.
3.2.4.4 Water Tank
[Operation Instructions]
★
At
the commissioning parameter setting page, by touching ―
Water tank
‖, the control panel will
access to the corresponding setting page, where ―
Water tank
‖ can be set to ―
With
‖ or ―
Without
‖.
[Notes]
●This setting will be memorized upon power failure.
●This setting will become valid only when the unit is turned off.
3.2.4.5 Thermostat
[Operation Instructions]
★
1. At the commissioning parameter setting page, by touching ―
Thermostat
‖, the control panel will
Summary of Contents for VERSATI III Series
Page 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Page 5: ...Engineering Data ENGINEERING DATA ...
Page 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Page 22: ...Design and Selection DESIGN SELECTION ...
Page 33: ...Unit Control UNIT CONTROL ...
Page 72: ...Unit Control ...
Page 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Page 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Page 80: ...Unit Control ...
Page 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Page 82: ...Installation UNIT INSTALLATION ...
Page 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Page 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Page 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Page 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Page 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Page 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Page 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...