Unit Control
3.2.4.8 Remote Sensor
[Operation Instructions]
★
At the commissioning parameter setting page, by touching ―
Remote sensor
‖, the control panel will
access to the corresponding setting page, where it can be set to ―
With
‖ or ―
Without
‖.
[Notes]
●This setting will be memorized upon power failure.
●Only when ―
Remote sensor
‖ is set to ―
With
‖, the ―
Ctrl. State
‖ can be set to ―
T-room
‖.
3.2.4.9 Air Removal
[Operation Instructions]
★
At the commissioning parameter setting page, by touching ―
Air removal
‖, the control panel will access
to the corresponding setting
page, where it can be set to ―
On
‖ or ―
Off
‖.
[Notes]
● This setting will be memorized upon power failure.
● This setting can be done only when the unit is turned off. And when it is set to ―
On
‖, the unit is not
allowed to be turned on.
3.2.4.10 Floor Debug
[Operation Instructions]
★
1. At the commissioning parameter setting page, by touching ―
Floor debug
‖, the control panel will
access to the corresponding setting page.
★
2. At the setting page, ―
Floor debug
‖, ―
Segments
‖, ―
Period 1 temp
‖, ―
Segment time
‖, and ―
ΔT of
segment
‖ can be set.
No.
Full Name
Displayed Name
Range
Default
Accuracy
1
Floor debug switch
Floor debug
On/Off
Off
/
2
Quantity of segments
Segments
1~10
1
1
3
Temperature of the first
Period 1 temp
25~35
℃
/
25
℃
/
1
℃
Summary of Contents for VERSATI III Series
Page 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Page 5: ...Engineering Data ENGINEERING DATA ...
Page 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Page 22: ...Design and Selection DESIGN SELECTION ...
Page 33: ...Unit Control UNIT CONTROL ...
Page 72: ...Unit Control ...
Page 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Page 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Page 80: ...Unit Control ...
Page 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Page 82: ...Installation UNIT INSTALLATION ...
Page 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Page 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Page 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Page 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Page 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Page 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Page 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...