Test Operation & Troubleshooting & Maintenance
hydraulics system pressure according to next item:
①
If the pressure is less than 0.5 bar, please recharge the water immediately;
②
When recharging, the hydraulics system pressure should be not more than 2.5 Bar.
5.2 Troubleshooting
Malfunctions
Reasons
Troubleshooting
Compressor does
not start up
Power supply has problem.
Connection wire is loose.
Malfunction of mainboard.
Malfunction of compressor.
Phase sequence is reverse.
Check out and re-fix.
Find out the reasons and repair.
Replace compressor.
Heavy noise of fan
Fixing bolt of fan is loose.
Fan blade touches shell or grill.
Operation of fan is unreliable.
Re-fix fixing bolt of fan.
Find out the reasons and adjust.
Replace fan.
Heavy noise of
compressor
Liquid slugging happens when liquid
refrigerant enters into compressor.
Internal parts in compressor are broken.
Check if expansion valve is failure and
temp. sensor is loose. If that, repair it.
Replace compressor.
Water pump does
not run or runs
abnormally
Malfunction of power supply or terminal.
Malfunction of relay.
There is air in water pipe.
Find out the reasons and repair.
Replace relay.
Evacuate.
Compressor starts or
stops frequently
Poor or excess refrigerant.
Poor circulation of water system.
Low load.
Discharge or add part of refrigerant.
Water system is blocked or there is air in
it. Check water pump, valve and pipeline.
Clean water filter or evacuate.
Adjust the load or add accumulating
devices.
The unit does not
heat although
compressor is
running
Leakage of refrigerant.
Malfunction of compressor.
Repair by leakage detection and add
refrigerant.
Replace compressor.
Poor efficiency of hot
water heating
Poor heat insulation of water system.
Poor heat exchange of evaporator.
Poor refrigerant of unit.
Blockage of heat exchanger at water
side.
Enhance heat insulation efficiency of the
system.
Check if air in or out of unit is normal and
clean evaporator of the unit.
Check if refrigerant of unit leaks.
Clean or replace heat exchanger.
Summary of Contents for VERSATI III Series
Page 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Page 5: ...Engineering Data ENGINEERING DATA ...
Page 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Page 22: ...Design and Selection DESIGN SELECTION ...
Page 33: ...Unit Control UNIT CONTROL ...
Page 72: ...Unit Control ...
Page 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Page 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Page 80: ...Unit Control ...
Page 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Page 82: ...Installation UNIT INSTALLATION ...
Page 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Page 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Page 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Page 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Page 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Page 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Page 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...