Installation
4.11 Wiring of the 2-Way Valve
The 2-way valve 1 is required to control water flow for cooling or heating operation. The role of 2-way
valve 1 is to cut off water flow into the underfloor loop when the fan coil unit is equipped for cooling
operation.
General Information
Type
Power
Operating Mode
Supported
NO 2-wire
230V 50Hz ~AC
Closing water flow
Yes
Opening water flow
Yes
NC 2-wire
230V 50Hz ~AC
Closing water flow
Yes
Opening water flow
Yes
(1) Normal Open type. When electric power is NOT supplied, the valve is open. (When electric
power is supplied, the valve is closed.)
(2) Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric
power is supplied, the valve is open.)
How to Wire 2-Way Valve:
Follow steps below to wire the 2-way valve.
Step 1. Uncover the front cover of the unit and open the control box.
Step 2. Find the terminal block and connect wires as below.
WARING!
(1) Normal Open type should be connected to wire (OFF) and wire (N) for valve closing in cooling
mode.
(2) Normal Closed type should be connected to wire (ON) and wire (N) for valve closing in cooling
mode.
(ON): Live signal (for Normal Open type) from PCB to 2-way valve
(OFF): Live signal (for Normal Closed type) from PCB to 2-way valve
(N): Neutral signal from PCB to 2-way valve
4.12 Wiring of the 3-Way Valve
The 3-way valve 2 is required for the sanitary water tank. Its role is flow switching between the under
floor heating loop and the water tank heating loop.
General Information
Type
Power
Operating Mode
Supported
SPDT 3-wire
230V 50Hz ~AC
Selecting ―Flow A‖ between ―Flow A‖ and ―Flow B‖
Yes
Selecting
―Flow B‖ between ―Flow B‖ and ―Flow A‖
Yes
(1) SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting Flow B), and
Neutral (for common).
(2) Flow A means 'water flow from the indoor unit to under floor water circ uit.
(3) Flow B means 'water flow from the indoor unit to sanitary water tank.
Summary of Contents for VERSATI III Series
Page 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Page 5: ...Engineering Data ENGINEERING DATA ...
Page 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Page 22: ...Design and Selection DESIGN SELECTION ...
Page 33: ...Unit Control UNIT CONTROL ...
Page 72: ...Unit Control ...
Page 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Page 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Page 80: ...Unit Control ...
Page 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Page 82: ...Installation UNIT INSTALLATION ...
Page 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Page 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Page 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Page 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Page 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Page 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Page 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...