Unit Control
[Notes]
● This function is allowed only when the unit has just repowered and not turned on. For the unit which
once has been put into operation, this function is unavailable, alerting ―
Wrong operation
‖.
● This function will not be memorized upon power failure.
3.2.4.17 Parameter Setting
[Operation Instructions]
★
At the commissioning parameter setting page, by touching ―PARAM.‖, it will access to the pages as
shown below.
Page of Commissioning Parameters
★
At this page, select the desired option and then go to the corresponding page.
★
After that, by pressing ―OK‖, this setting will be saved and then the unit will run based on this setting;
or by pressing ―Cancel‖, this setting will not be saved and quit.
No
Full Name
Display Name
Range
Default
Remark
1
T-HP max
T-HP max
40~55
℃
104~131
℉
50
℃
/122
℉
2
Cool run time
Cool run time
1~10min
3min
[2-way valve Off]
When ―Cool run time‖ has
expired and temperature
difference keeps at the
standby zone, the unit will
stop.
5min
[2-way valve On]
3
Heat run time
Heat run time
1~10min
3min
[2-way valve Off]
When ―Heat run time‖ has
expired and temperature
difference keeps at the
standby zone, the unit will
stop.
5min
[2-way valve On]
[Notes]
● For parameters with different defaults at different conditions, once the current condition changes, the
corresponding default also will change.
● All parameters at this page will be memorized upon power failure.
3.2.5 Viewing
[Operation Instructions]
★
1. At the menu page, by touching ―
VIEW
‖, the control panel will go to the sub-menu page as shown in
Summary of Contents for VERSATI III Series
Page 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Page 5: ...Engineering Data ENGINEERING DATA ...
Page 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Page 22: ...Design and Selection DESIGN SELECTION ...
Page 33: ...Unit Control UNIT CONTROL ...
Page 72: ...Unit Control ...
Page 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Page 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Page 80: ...Unit Control ...
Page 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Page 82: ...Installation UNIT INSTALLATION ...
Page 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Page 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Page 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Page 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Page 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Page 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Page 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...