Unit Control
default value also will change as the corresponding condition changes.
●
All parameters will be memorized upon power failure.
Parameter Setting
No
Full Name
Displayed Name
Range
Range
Default
Remarks
(
℃
)
(°F)
1
Leaving water
temperature for
cooling(T1)
WOT-Cool
7~25
℃
45~77
℉
18
℃
/64
℉
2
Leaving water
temperature for heating
(T2)
WOT-Heat
20~60
℃
68~140
℉
45
℃
/113
℉
High-temp
series units
20~55
℃
68~140
℉
45
℃
/113
℉
Normal-temp
series units
3
Room temperature for
cooling (T3)
RT-Cool
18~30
℃
64~86
℉
24
℃
/75
℉
4
Room temperature for
heating (T4)
RT-Heat
18~30
℃
64~86
℉
20
℃
/68
℉
5
Water tank
temperature(T5)
T-water tank
40~80
℃
104~176
℉
50
℃
/122
℉
6
Leaving water
temperature difference
for cooling (
Δt1)
ΔT-Cool
2~10
℃
36~50
℉
5
℃
/41
℉
7
Leaving water
temperature difference
for cooling (
Δt2)
ΔT-Heat
2~10
℃
36~50
℉
10
℃
/50
℉
8
Leaving water
temperature difference
for water heating (
Δt3)
ΔT-hot water
2~8
℃
36~46
℉
5
℃
/41
℉
9
Room temperature
control difference (
Δt4)
ΔT-Room temp
1~5
℃
34~41
℉
2
℃
/36
℉
3.2.4 Commissioning Parameter Setting
[Operation Instructions]
★
1. At the menu page, by touching ―
Commission
‖, it will access to the commissioning parameter page,
where the left side is for the function setting and the right side is for the parameter setting, as shown in
the figure below.
Summary of Contents for VERSATI III Series
Page 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Page 5: ...Engineering Data ENGINEERING DATA ...
Page 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Page 22: ...Design and Selection DESIGN SELECTION ...
Page 33: ...Unit Control UNIT CONTROL ...
Page 72: ...Unit Control ...
Page 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Page 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Page 80: ...Unit Control ...
Page 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Page 82: ...Installation UNIT INSTALLATION ...
Page 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Page 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Page 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Page 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Page 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Page 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Page 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...