Unit Control
3.2.4.13 Gate-Ctrl.
[Operation Instructions]
★
At the commissioning parameter setting page, by touching ―
Gate-Ctrl.
‖, the control panel will access
to the corresponding setting page.
[Notes]
●When ―
Gate-Ctrl.
‖ has been activated; the display panel will detect the card state. When the card has
inserted, the unit will run normally. When the card is drawn out, the controller will turn off the unit at
once and back to the homepage. In this case, all touching operation become ineffective, and a prompt
dialog box will pop up. The unit will resume normal operation until the card has inserted back and the
ON/OFF status of the control panel will resume to that before the card is drawn out.
●This setting will be memorized upon power failure.
3.2.4.14 Current Limit
[Operation Instructions]
★
1. At the commissioning parameter setting page, by touching ―
Current limit
‖, it can be set to ―
On
‖ or
―
Off
‖.
★
2. When it is set to ―
On
‖, it is able to set the limited current value.
★
3. After that, this setting will be saved by touching the ―
Save
‖ icon,
[Notes]
● This setting will be memorized upon power failure.
3.2.4.15 Address
[Operation Instructions]
★
At the commissioning parameter setting page, by tou
ching ―
Current limit
‖, it can be set the address.
[Notes]
:
● It is used to set the address of the control panel for being integrated to the centralized control system.
● This setting will be memorized upon power failure.
● The setting range is 1~125 and 127~253.
● The defaulted address is 1 upon first power-on.
3.2.4.16 Refrigerant Recovery
[Operation Instructions]
★
At the commissioning parameter setting page, by touching ―
Refri. recovery
‖, it will access to the
refrigerant recovery page.
★
When ―
Refri. recovery
‖ is set to ―
On
‖, the control panel will go back to the home page. At this time,
any touch operation except ON/OFF will get no response, with a prompt dialog box popping up,
saying ―
The refrigerant recovery is running!
‖ By touching ON/OFF, refrigerant recovery will quit.
Summary of Contents for VERSATI III Series
Page 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Page 5: ...Engineering Data ENGINEERING DATA ...
Page 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Page 22: ...Design and Selection DESIGN SELECTION ...
Page 33: ...Unit Control UNIT CONTROL ...
Page 72: ...Unit Control ...
Page 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Page 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Page 80: ...Unit Control ...
Page 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Page 82: ...Installation UNIT INSTALLATION ...
Page 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Page 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Page 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Page 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Page 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Page 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Page 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...