GE Multilin
C70 Capacitor Bank Protection and Control System
9-9
9 THEORY OF OPERATION
9.1 OVERVIEW
9
Under normal system conditions (non-fault),
V
C
>>
V
0
, and
V
C
is the system phase-to-ground voltage. The system voltage
V
Spg
, which by convention is on the bus voltage base, converted to the base of nominal value of the neutral-point VT used
in these equations, is:
(EQ 9.39)
This gives:
(EQ 9.40)
This can be written as:
(EQ 9.41)
In the above equations,
Δ
C
(pu) is the capacitance change as a per-unit of the leg capacitance, and
V
OP
(pu) is the operating
signal resulting from the failure in per-unit of the nominal value of the neutral-point VT.
V
Spg
is the system phase-to-ground
voltage in per-unit of the nominal system phase-to-ground voltage, so can be taken as 1 when the system is normal (not
faulted). Note however that under external fault conditions sensitivity may be much different from the non-fault sensitivity.
n
bus_phs
and
n
ntrl_aux
are the VT ratios of the phase VT bank of the bus source and of the auxiliary VT channel of the neutral
source, respectively.
Note that under external fault conditions sensitivity may be much different form the non-fault sensitivity. To prevent mis-
operation, a restraint and/or coordinating time delay should be used.
d) RESTRAINT
Severe system voltage unbalance, such as can occur during near-by bolted ground faults, can exacerbate measurement
error in
V
X
or
V
0
, resulting in spurious operating signal. In addition as discussed above the sensitivity can be affected. To
prevent operation under these conditions, percent restraint supervision is provided using a restraint signal that is the mag-
nitude of the vector sum of
V
X
and
V
0
, as defined below.
(EQ 9.42)
During external ground faults, these two voltages are approximately in phase generating a large restraining signal being
twice the zero-sequence voltage at the bus. A slope of few percent is typically sufficient to provide good security under
large system unbalances.
Figure 9–4: NEUTRAL OVERVOLTAGE RESTRAINT
e) AUTO-SETTING COMMAND
As a convenient alternative to manually determining the unbalance ratio settings, the relay can automatically calculate
these settings from its own measurements while the capacitor is in-service, as described in the
Commands
chapter. The
technique the relay uses is to set the operate signal variable in equation 8.25 to zero and solve for the unbalance ratio
k
-
values using the average of several successive measurements of the voltages.
n
bus_phs
n
ntrl_aux
--------------------
V
Spg
×
d
dC
C
-----------
V
OP
1
3
---
1
C
C
-------
n
bus_phs
n
ntrl_aux
--------------------
V
Spg
×
×
×
≅
dV
OP
1
3
---
n
bus_phs
n
ntrl_aux
--------------------
V
Spg
×
×
dC
C
C
C
-----------
×
≅
⇒
V
OP
pu
(
)
1
3
---
n
bus_phs
n
ntrl_aux
--------------------
V
Spg
×
×
C
pu
(
)
Δ
×
≅
V
REST
V
X
V
0
+
=
834746A1.CDR
V
REST
V
OP
NTRL VOLT PKP
Slope settin
g
Pickup
setting
NTRL VOLT DPO
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...