The GGIO5 integer configuration points are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
ÖØ
GGIO5 ANALOG CONFIGURATION
The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the C70. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
•
GGIO5 UINT IN 1 VALUE
: This setting selects the FlexInteger™ value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
The report control configuration settings are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
ÖØ
REPORT...
Ö
REPORT 1(6) CONFIGURATION
Changes to the report configuration will not take effect until the C70 is restarted.
Please disconnect any IEC 61850 client connection to the C70 prior to making setting changes to the report config-
uration. Disconnecting the rear Ethernet connection from the C70 will disconnect the IEC 61850 client connection.
GGIO5 UINTEGER
CONFIGURATION
GGIO5 UINT In 1:
Off
Range: Off, any FlexInteger parameter
MESSAGE
GGIO5 UINT In 2:
Off
Range: Off, any FlexInteger parameter
↓
MESSAGE
GGIO5 UINT 1n 16:
Off
Range: Off, any FlexInteger parameter
REPORT 1
CONFIGURATION
REPORT 1
RptID:
Range: up to 66 alphanumeric characters
MESSAGE
REPORT 1
OptFlds:
0
Range: 0 to 65535 in steps of 1
MESSAGE
REPORT 1
BufTm:
0
Range: 0 to 4294967295 in steps of 1
MESSAGE
REPORT 1
TrgOps:
0
Range: 0 to 65535 in steps of 1
MESSAGE
REPORT 1
IntgPd:
0
Range: 0 to 4294967295 in steps of 1
NOTE