B-22
C70 Capacitor Bank Protection and Control System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
42C6
...Repeated for User-Programmable LED 36
42C8
...Repeated for User-Programmable LED 37
42CA
...Repeated for User-Programmable LED 38
42CC
...Repeated for User-Programmable LED 39
42CE
...Repeated for User-Programmable LED 40
42D0
...Repeated for User-Programmable LED 41
42D2
...Repeated for User-Programmable LED 42
42D4
...Repeated for User-Programmable LED 43
42D6
...Repeated for User-Programmable LED 44
42D8
...Repeated for User-Programmable LED 45
42DA
...Repeated for User-Programmable LED 46
42DC
...Repeated for User-Programmable LED 47
42DE
...Repeated for User-Programmable LED 48
Installation (Read/Write Setting)
43E0
Relay Programmed State
0 to 1
---
1
F133
0 (Not Programmed)
43E1
Relay Name
---
---
---
F202
“Relay-1”
User Programmable Self Tests (Read/Write Setting)
4441
User Programmable Detect Ring Break Function
0 to 1
---
1
F102
1 (Enabled)
4442
User Programmable Direct Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4443
User Programmable Remote Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4444
User Programmable Primary Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4445
User Programmable Secondary Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4446
User Programmable Battery Fail Function
0 to 1
---
1
F102
1 (Enabled)
4447
User Programmable SNTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
4448
User Programmable IRIG-B Fail Function
0 to 1
---
1
F102
1 (Enabled)
4449
User Programmable Ethernet Switch Fail Function
0 to 1
---
1
F102
0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480
Phase CT 1 Primary
1 to 65000
A
1
F001
1
4481
Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4482
Ground CT 1 Primary
1 to 65000
A
1
F001
1
4483
Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4484
...Repeated for CT Bank 2
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500
Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
4501
Phase VT 1 Secondary
50 to 240
V
0.1
F001
664
4502
Phase VT 1 Ratio
1 to 24000
:1
1
F060
1
4504
Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
4505
Auxiliary VT 1 Secondary
50 to 240
V
0.1
F001
664
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
---
---
---
F206
“SRC 1"
4583
Source 1 Phase CT
0 to 63
---
1
F400
0
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...