GE Multilin
C70 Capacitor Bank Protection and Control System
2-1
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
2
2 PRODUCT DESCRIPTION 2.1INTRODUCTION
2.1.1 OVERVIEW
The C70 Capacitor Bank Protection and Control System is a UR-series microprocessor-based relay for protection and con-
trol of small, medium, and large three-phase capacitor banks. The relay can be ordered with up to three CT/VT modules,
allowing for flexible application to variety of bank configurations.
The key protection functions are designed to cover grounded and ungrounded, single and parallel banks. Sensitive protec-
tion functions support compensation for both external (system) unbalance and inherent unbalance of the capacitor bank
itself. Both voltage and current-based balance protection functions are available. Algorithms are developed to automatically
select compensation settings after repairs or other alternations of the bank.
The relay supports variety of bank configurations through flexible configurations of its AC inputs, installed voltage and cur-
rent transformers, and resulting protection techniques.
The relay incorporates an
automatic voltage regulator
(AVR) responding to either voltage, reactive power, or power factor.
A separate timer function initiates controls on a pre-defined time/date basis. These on-off type controls are meant to auto-
matically close or open the associated breaker. A supervisory function is provided to program the local/remote, auto/man-
ual functionality, temporary inhibit closing after tripping, and other auxiliary functions such as operation counters.
A capacitor control element provides remote/local and auto/manual control regulation, trip/close interlocking, and seal-in. A
user-programmable time delay inhibits closing until after the bank discharges itself to a safe level.
Up to six contact input/output modules can be ordered. The relay can also equipped with a serial 64/128 kbps direct input/
output module for fast and reliable peer-to-peer communication with other UR-series IEDs.
The C70 metering functions include true RMS and phasors for currents and voltages, current and voltage harmonics and
THD, symmetrical components, frequency, power, power factor.
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of storing
up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16 channels,
with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized with an IRIG-
B signal or via the SNTP protocol over the Ethernet port. This precise time stamping allows the sequence of events to be
determined throughout the system. Events can also be programmed (via FlexLogic™) to trigger oscillography data capture
which may be set to record the measured parameters before and after the event for viewing on a personal computer. These
tools significantly reduce troubleshooting time and simplify report generation in the event of a system fault.
A faceplate RS232 port may be used to connect to a PC for the programming of settings and the monitoring of actual val-
ues. A variety of communications modules are available. Two rear RS485 ports allow independent access by operating and
engineering staff. All serial ports use the Modbus
®
RTU protocol. The RS485 ports may be connected to system computers
with baud rates up to 115.2 kbps. The RS232 port has a fixed baud rate of 19.2 kbps. Optional communications modules
include a 10/100Base-T or 10Base-F Ethernet interface which can be used to provide fast, reliable communications in
noisy environments. Another option provides two 10BaseF fiber optic ports for redundancy. The Ethernet port supports IEC
61850, Modbus
®
/TCP, and TFTP protocols, and allows access to the relay via any standard web browser (C70 web pages).
The IEC 60870-5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the
same time.
The C70 IEDs use flash memory technology which allows field upgrading as new features are added. The following single
line diagram illustrates the relay functionality using ANSI (American National Standards Institute) device numbers.
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...