GE Multilin
C70 Capacitor Bank Protection and Control System
5-75
5 SETTINGS
5.4 SYSTEM SETUP
5
•
SWITCH 1 OPEN:
This setting selects an operand that creates a programmable signal to operate an output relay to
open disconnect switch 1.
•
SWITCH 1 BLK OPEN
: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWITCH 1 CLOSE:
This setting selects an operand that creates a programmable signal to operate an output relay to
close disconnect switch 1.
•
SWITCH 1 BLK CLOSE
: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWTCH 1
Φ
A/3P CLSD:
This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when
the disconnect switch is closed. If the
SWITCH 1 MODE
setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the
SWITCH 1
Φ
B
and
SWITCH 1
Φ
C
settings select operands to
track phases B and C, respectively.
•
SWITCH 1
Φ
A/3P OPND:
This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the disconnect switch is open. If a separate 52/b contact input is not avail-
able, then the inverted
SWITCH 1 CLOSED
status signal can be used.
•
SWITCH 1
Φ
B CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
•
SWITCH 1
Φ
B OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
•
SWITCH 1
Φ
C CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
•
SWITCH 1
Φ
C OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
•
SWITCH 1 Toperate
: This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the
SWITCH 1 BAD STATUS
FlexLogic™ operand is asserted from alarm or blocking purposes.
•
SWITCH 1 ALARM DELAY:
This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the C70 is in “Programmed” mode and not in the local control mode.
NOTE
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...