GE Multilin
C70 Capacitor Bank Protection and Control System
5-45
5 SETTINGS
5.2 PRODUCT SETUP
5
Refer to the
Control of setting groups
example in the
Control elements
section of this chapter for group activation.
5.2.11 USER-PROGRAMMABLE SELF TESTS
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
USER-PROGRAMMABLE SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the minor alarms can be disabled if desired.
When in the “Disabled” mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the
ANY MINOR ALARM
or
ANY SELF-TEST
messages. When in the “Enabled”
mode, minor alarms continue to function along with other major and minor alarms. Refer to the
Relay self-tests
section in
chapter 7 for additional information on major and minor self-test alarms.
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
REMOTE DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
MESSAGE
PRI. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
MESSAGE
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
MESSAGE
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
MESSAGE
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
ETHERNET SWITCH FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...