GE Multilin
C70 Capacitor Bank Protection and Control System
5-25
5 SETTINGS
5.2 PRODUCT SETUP
5
1.
Configure the transmission dataset.
2.
Configure the GOOSE service settings.
3.
Configure the data.
The general steps required for reception configuration are:
1.
Configure the reception dataset.
2.
Configure the GOOSE service settings.
3.
Configure the data.
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1.
Configure the transmission dataset by making the following changes in the
PRODUCT SETUP
ÖØ
COMMUNICATION
ÖØ
IEC 61850 PROTOCOL
Ö
GSSE/GOOSE CONFIGURATION
Ö
TRANSMISSION
ÖØ
CONFIGURABLE GOOSE
Ö
CONFIGURABLE
GOOSE 1
ÖØ
CONFIG GSE 1 DATASET ITEMS
settings menu:
–
Set
ITEM 1
to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
–
Set
ITEM 2
to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
The transmission dataset now contains a set of quality flags and a single point status Boolean value. The reception
dataset on the receiving device must exactly match this structure.
2.
Configure the GOOSE service settings by making the following changes in the
PRODUCT SETUP
ÖØ
COMMUNICATION
ÖØ
IEC 61850 PROTOCOL
Ö
GSSE/GOOSE CONFIGURATION
Ö
TRANSMISSION
ÖØ
CONFIGURABLE GOOSE
Ö
CONFIGU-
RABLE GOOSE 1
settings menu:
–
Set
CONFIG GSE 1 FUNCTION
to “Enabled”.
–
Set
CONFIG GSE 1 ID
to an appropriate descriptive string (the default value is “GOOSEOut_1”).
–
Set
CONFIG GSE 1 DST MAC
to a multicast address (for example, 01 00 00 12 34 56).
–
Set the
CONFIG GSE 1 VLAN PRIORITY
; the default value of “4” is OK for this example.
–
Set the
CONFIG GSE 1 VLAN ID
value; the default value is “0”, but some switches may require this value to be “1”.
–
Set the
CONFIG GSE 1 ETYPE APPID
value. This setting represents the ETHERTYPE application ID and must match
the configuration on the receiver (the default value is “0”).
–
Set the
CONFIG GSE 1 CONFREV
value. This value changes automatically as described in IEC 61850 part 7-2. For
this example it can be left at its default value.
3.
Configure the data by making the following changes in the
PRODUCT SETUP
ÖØ
COMMUNICATION
ÖØ
IEC 61850 PROTO-
COL
Ö
GGIO1 STATUS CONFIGURATION
settings menu:
–
Set
GGIO1 INDICATION 1
to a FlexLogic™ operand used to provide the status of GGIO1.ST.Ind1.stVal (for example,
a contact input, virtual input, a protection element status, etc.).
The C70 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1.
Configure the reception dataset by making the following changes in the
PRODUCT SETUP
ÖØ
COMMUNICATION
ÖØ
IEC
61850 PROTOCOL
Ö
GSSE/GOOSE CONFIGURATION
ÖØ
RECEPTION
ÖØ
CONFIGURABLE GOOSE
Ö
CONFIGURABLE GOOSE
1
ÖØ
CONFIG GSE 1 DATASET ITEMS
settings menu:
–
Set
ITEM 1
to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
–
Set
ITEM 2
to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2.
Configure the GOOSE service settings by making the following changes in the
INPUTS/OUTPUTS
ÖØ
REMOTE DEVICES
ÖØ
REMOTE DEVICE 1
settings menu:
–
Set
REMOTE DEVICE 1 ID
to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...