GE Multilin
745 Transformer Management Relay
7-43
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
FREQUENCY
DECAY
22C8
Reserved
↓
↓
↓
↓
↓
↓
↓
22CF
Reserved
22D0
Frequency Decay Function
---
---
---
F30
0 = Disabled
22D1
Frequency Decay Target
---
---
---
F46
1 = Latched
22D2
Frequency Decay Minimum Operating Current
0.05 to 1.00
0.01
×
CT
F3
20 = 0.20
×
CT
22D3
Frequency Decay Threshold
45.00 to 59.99
0.01
Hz
F3
5950 = 59.5 Hz
22D4
Frequency Decay Rate 1
0.1 to 5.0
0.1
Hz/s
F2
4 = 0.4 Hz/s
22D5
Frequency Decay Rate 2
0.1 to 5.0
0.1
Hz/s
F2
10 = 1.0 Hz/s
22D6
Frequency Decay Rate 3
0.1 to 5.0
0.1
Hz/s
F2
20 = 2.0 Hz/s
22D7
Frequency Decay Rate 4
0.1 to 5.0
0.1
Hz/s
F2
40 = 4.0 Hz/s
22D8
Frequency Decay Block
---
---
---
F87
0 = Disabled
22D9
Frequency Decay Current Sensing
---
---
---
F30
1 = Enabled
22DA
Frequency Decay Minimum Operating Voltage
0.10 to 0.99
0.01
×
VT
F3
50 = 0.50
×
VT
22DB
Frequency Decay Delay
0.00 to 600.00
0.01
s
F3
0 = 0.00 s
22DC
Reserved
↓
↓
↓
↓
↓
↓
↓
22DF
Reserved
OVER-
FREQUENCY
22E0
Overfrequency Function
---
---
---
F30
0 = Disabled
22E1
Overfrequency Target
---
---
---
F46
1 = Latched
22E2
Overfrequency Minimum Operating Current
0.05 to 1.00
0.01
×
CT
F3
20 = 0.20
×
CT
22E3
Overfrequency Pickup
50.01 to 65.00
0.01
Hz
F3
6050 = 60.5 Hz
22E4
Overfrequency Delay
0.00 to 600.00
0.01
s
F3
500 = 5.00 s
22E5
Overfrequency Block
---
---
---
F87
0 = Disabled
22E6
Overfrequency Current Sensing
---
---
---
F30
1 = Enabled
22E7
Overfrequency Minimum Operating Voltage
0.10 to 0.99
0.01
×
VT
F3
50 = 0.50
×
VT
22E8
Reserved
↓
↓
↓
↓
↓
↓
↓
22EF
Reserved
5th HARMONIC
LEVEL
22F0
5th Harmonic Level Function
---
---
---
F30
0 = Disabled
22F1
5th Harmonic Level Target
---
---
---
F46
0 = Self-reset
22F2
5th Harmonic Level Min.Operating Current
0.03 to 1.00
0.01
×
CT
F3
10 = 0.10
×
CT
22F3
5th Harmonic Level Pickup
0.1 to 99.9
0.1
% ƒo
F1
100 = 10.0% ƒo
22F4
5th Harmonic Level Delay
0 to 60000
1
s
F1
10 s
22F5
5th Harmonic Level Block
---
---
---
F87
0 = Disabled
22F6
Reserved
↓
↓
↓
↓
↓
↓
↓
22FF
Reserved
VOLTS-PER-
HERTZ 1
2300
Volts-Per-Hertz 1 Function
---
---
---
F30
0 = Disabled
2301
Volts-Per-Hertz 1 Target
---
---
---
F46
0 = Self-reset
2302
Volts-Per-Hertz 1 Minimum Operating Voltage
0.10 to 0.99
0.01
×
VT
F3
10 = 0.10
×
VT
2303
Volts-Per-Hertz 1 Pickup
1.00 to 4.00
0.01
V/Hz
F3
236 = 2.36 V/Hz
2304
Volts-Per-Hertz 1 Shape
---
---
---
F86
0 = Def. Time
2305
Volts-Per-Hertz 1 Delay
0.00 to 600.00
0.01
s
F3
200 = 2.00 s
2306
Volts-Per-Hertz 1 Reset
0.0 to 6000.0
0.1
s
F2
0.0 s
2307
Volts-Per-Hertz 1 Block
---
---
---
F87
0 = Disabled
2308
Reserved
↓
↓
↓
↓
↓
↓
↓
230F
Reserved
Table 7–5: 745 MEMORY MAP (Sheet 31 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT