7-16
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
WINDING 1
CURRENT
0280
Winding 1 Phase A Current - Magnitude
---
---
A
F78
---
0281
Winding 1 Phase A Current - Angle
0
---
° Lag
F1
---
0282
Winding 1 Phase B Current - Magnitude
---
---
A
F78
---
0283
Winding 1 Phase B Current - Angle
0 to 359
1
° Lag
F1
---
0284
Winding 1 Phase C Current - Magnitude
---
---
A
F78
---
0285
Winding 1 Phase C Current - Angle
0 to 359
1
° Lag
F1
---
0286
Winding 1 Neutral Current - Magnitude
---
---
A
F78
---
0287
Winding 1 Neutral Current - Angle
0 to 359
1
° Lag
F1
---
0288
Winding 1 Ground Current - Magnitude
---
---
A
F81
---
0289
Winding 1 Ground Current - Angle
0 to 359
1
° Lag
F1
---
028A
Winding 1 Loading
0 to 999
1
% rated
F1
---
028B
Winding 1 Ave. Phase Current
---
---
A
F78
---
028C
Reserved
028F
Reserved
WINDING 2
CURRENT
0290
Winding 2 Phase A Current - Magnitude
---
---
A
F79
---
0291
Winding 2 Phase A Current - Angle
0 to 359
1
° Lag
F1
---
0292
Winding 2 Phase B Current - Magnitude
---
---
A
F79
---
0293
Winding 2 Phase B Current - Angle
0 to 359
1
° Lag
F1
---
0294
Winding 2 Phase C Current - Magnitude
---
---
A
F79
---
0295
Winding 2 Phase C Current - Angle
0 to 359
1
° Lag
F1
---
0296
Winding 2 Neutral Current - Magnitude
---
---
A
F79
---
0297
Winding 2 Neutral Current - Angle
0 to 359
1
° Lag
F1
---
0298
Winding 2 Ground Current - Magnitude
---
---
A
F82
---
0299
Winding 2 Ground Current - Angle
0 to 359
1
° Lag
F1
---
029A
Winding 2 Loading
0 to 999
1
% rated
F1
---
029B
Winding 2 Ave. Phase Current
---
---
A
F79
---
029C
Reserved
029F
Reserved
WINDING 3
CURRENT
02A0
Winding 3 Phase A Current - Magnitude
---
---
A
F80
---
02A1
Winding 3 Phase A Current - Angle
0 to 359
1
° Lag
F1
---
02A2
Winding 3 Phase B Current - Magnitude
---
---
A
F80
---
02A3
Winding 3 Phase B Current - Angle
0 to 359
1
° Lag
F1
---
02A4
Winding 3 Phase C Current - Magnitude
---
---
A
F80
---
02A5
Winding 3 Phase C Current - Angle
0 to 359
1
° Lag
F1
---
02A6
Winding 3 Neutral Current - Magnitude
---
---
A
F80
---
02A7
Winding 3 Neutral Current - Angle
0 to 359
1
° Lag
F1
---
02A8
Winding 3 Ground Current - Magnitude
---
---
A
F83
---
02A9
Winding 3 Ground Current - Angle
0 to 359
1
° Lag
F1
---
02AA
Winding 3 Loading
0 to 999
1
% rated
F1
---
02AB
Winding 3 Ave. Phase Current
---
---
A
F80
---
02AC
Reserved
02AF
Reserved
SEQUENCE
CURRENTS
02B0
Winding 1 Positive Sequence Current Magnitude
---
---
A
F78
---
02B1
Winding 1 Positive Sequence Current Angle
0 to 359
1
° Lag
F1
---
02B2
Winding 2 Positive Sequence Current Magnitude
---
---
A
F79
---
02B3
Winding 2 Positive Sequence Current Angle
0 to 359
1
° Lag
F1
---
02B4
Winding 3 Positive Sequence Current Magnitude
---
---
A
F80
---
02B5
Winding 3 Positive Sequence Current Angle
0 to 359
1
° Lag
F1
---
02B6
Winding 1 Negative Sequence Current Mag
---
---
A
F78
---
02B7
Winding 1 Negative Sequence Current Angle
0 to 359
1
° Lag
F1
---
02B8
Winding 2 Negative Sequence Current Mag
---
---
A
F79
---
02B9
Winding 2 Negative Sequence Current Angle
0 to 359
1
° Lag
F1
---
02BA
Winding 3 Negative Sequence Current Mag
---
---
A
F80
---
02BB
Winding 3 Negative Sequence Current Angle
0 to 359
1
° Lag
F1
---
02BC
Winding 1 Zero Sequence Current Magnitude
---
---
A
F78
---
Table 7–5: 745 MEMORY MAP (Sheet 4 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT