5-84
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
5.6.14 ANALOG LEVEL
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
ANALOG INPUT
Ö
ANALOG LEVEL 1(2)
The 745 can monitor any external quantity, such as bus voltage, battery voltage, etc., via a general purpose auxiliary cur-
rent input called the analog input. Any one of the standard transducer output ranges 0-1 mA, 0-5 mA, 4-20 mA, or 0-20 mA
can be connected to the analog input terminals. The analog input is configured in
S2 SYSTEM SETUP
ÖØ
ANALOG INPUT
and
the actual values displayed in
A2 METERING
ÖØ
ANALOG INPUT
.
Figure 5–39: ANALOG LEVEL SCHEME LOGIC
ANALOG LEVEL 1
[ENTER] for more
ANALOG LEVEL 1
FUNCTION: Disabled
Range: Enabled, Disabled
ANALOG LEVEL 1
TARGET: Self-Reset
Range: Self-Reset, Latched, None
ANALOG LEVEL 1
PICKUP: 10
µ
A
Range: 1 to 65000
µ
A in steps of 1
ANALOG LEVEL 1
DELAY: 50 s
Range: 0 to 60000 s in steps of 1
ANALOG LEVEL 1
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE