5-72
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
•
MINIMUM OPERATING CURRENT
: Enter the minimum value of Winding 1 Phase A current (in units of relay nominal
current) required to allow the overfrequency element to operate.
•
MINIMUM OPERATING VOLTAGE
: Enter the minimum value of voltage (in units of relay nominal voltage) required to
allow the underfrequency element to operate.
•
OVERFREQUENCY PICKUP
: Enter the frequency (in Hz) above which the overfrequency element will pickup and
start the delay timer.
•
OVERFREQUENCY DELAY
: Enter the time that the frequency must remain above the pickup level before the element
operates.
Figure 5–31: OVERFREQUENCY SCHEME LOGIC