GE Multilin
745 Transformer Management Relay
5-91
5 SETPOINTS
5.7 S5 OUTPUTS
5
•
OUTPUT 1(8) TYPE
: Select "Trip" to turn the Trip LED on or "Alarm" to turn the Alarm LED on when this output oper-
ates. Otherwise, select "Control". Note that the Trip LED remains on until a reset command is issued (or automatically
after one week). The Alarm LED turns off automatically when the output is no longer operated.
•
OUTPUT 1(8) FLEXLOGIC 01 to 20
: The 20 messages shown in the table below are the parameters of the Flex-
Logic™ equation for Output 1(8) as described in the introduction to FlexLogic™.
Figure 5–45: OUTPUT RELAYS SCHEME LOGIC
Table 5–14: OUTPUT RELAY DEFAULT FLEXLOGIC™
FLEXLOGIC™
GATE
OUTPUT RELAY NUMBER
1 TO 3
4
5
6
7
8
01
Percent Diff OP
Volts/Hertz 1 OP
W1 THD Level OP
Underfreq 1 OP
Underfreq 2 OP
Freq Decay 3 OP
02
Inst Diff OP
Volts/Hertz 2 OP
W2 THD Level OP Freq Decay R1 OP Freq Decay R2 OP
END
03
Any W1 OC OP
OR (2 inputs)
Xfmr Overload OP
OR (2 inputs)
OR (2 inputs)
END
04
Any W2 OC OP
END
5th HarmLevel OP
END
END
END
05
OR (4 inputs)
END
OR (4 inputs)
END
END
END
06 to 20
END
END
END
END
END
END