5-74
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
b) 5TH HARMONIC LEVEL
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
OVEREXCITATION
Ö
5th HARMONIC LEVEL
•
MINIMUM OPERATING CURRENT
: Enter the minimum value of current (in units of relay nominal current) required to
allow the 5th harmonic level element to operate.
•
5TH HARMONIC LEVEL PICKUP
: Enter the 5th harmonic current (in %ƒ
0
) above which the 5th harmonic level ele-
ment will pickup and start the delay timer.
•
5TH HARMONIC LEVEL DELAY
: Enter the time that the 5th harmonic current must remain above the pickup level
before the element operates.
Figure 5–32: 5TH HARMONIC LEVEL SCHEME LOGIC
5th HARMONIC LEVEL
[ENTER] for more
5th HARMONIC LEVEL
FUNCTION: Disabled
Range: Enabled, Disabled
5th HARMONIC LEVEL
TARGET: Self-Reset
Range: Self-Reset, Latched, None
MINIMUM OPERATING
CURRENT: 0.10 x CT
Range: 0.03 to 1.00 x CT in steps of 0.01
5th HARMONIC LEVEL
PICKUP: 10.0% f0
Range: 0.1 to 99.9% f
0
in steps of 0.1
5th HARMONIC LEVEL
DELAY: 10 s
Range: 0 to 60000 s in steps of 1
5th HARMONIC LEVEL
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled