5-82
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
c) AGING FACTOR LIMIT
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
INSULATION AGING
ÖØ
AGING FACTOR LIMIT
The Aging Factor Limit element provides a means of detecting when a transformer is aging faster than would normally be
acceptable. The element operates on the computed aging factor, which in turn is derived from the computed hottest-spot
value.
The aging factor value will revert to zero if the power supply to the relay is interrupted
. The necessary settings
required for this element to perform correctly are entered under:
•
AGING FACTOR LIMIT PICKUP
: Enter the Aging Factor required for operation of the element. This setting should be
above the maximum permissible aging factor under emergency loading condition and maximum ambient temperature.
•
AGING FACTOR LIMIT DELAY
: Enter a time delay above which the Aging Factor must remain before the element
operates.
Figure 5–37: AGING FACTOR LIMIT SCHEME LOGIC
AGING FACTOR LIMIT
[ENTER] for more
AGING FACTOR LIMIT
FUNCTION: Disabled
Range: Enabled, Disabled
AGING FACTOR LIMIT
TARGET: Self-Reset
Range: Self-Reset, Latched, None
AGING FACTOR LIMIT
PICKUP: 2.0
Range: 1.1 to 10 in steps of 0.1
AGING FACTOR LIMIT
DELAY: 10 min.
Range: 0 to 60000 min. in steps of 1
AGING FACTOR LIMIT
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE